RTDs vs Thermistors: Pt100 Classes, 2-, 3- and 4-Wire Connections, NTC Behaviour and How to Choose

On this page

Resistance temperature detectors (RTDs) and thermistors both measure temperature through a change in electrical resistance, but they behave very differently. Platinum RTDs are the industrial standard for accurate, stable measurement from cryogenic to several hundred degrees. Thermistors are very sensitive over a narrow range and are common in equipment, motors and electronics rather than in process piping.

RTDs vs Thermistors: RTD (for example Pt100) (Platinum resistance, About −200 to 600 °C and beyond); Thermistor (Semiconductor NTC or PTC, Narrow range)
RTDs suit accurate process measurement; thermistors suit sensitive, narrow-range uses.

RTDs: platinum resistance thermometers

  • A Pt100 has 100 Ω at 0 °C; a Pt1000 has 1,000 Ω. Resistance rises almost linearly with temperature.
  • The industrial standard curve (IEC 60751) has a mean temperature coefficient of 0.00385 Ω/Ω/°C, so a Pt100 changes by about 0.385 Ω per °C.
  • Construction: wire-wound (high accuracy, wide range) or thin-film (robust, small, low cost).

Tolerance classes (IEC 60751)

Class Tolerance At 100 °C
AA ±(0.10 + 0.0017 × |t|) °C ±0.27 °C
A ±(0.15 + 0.002 × |t|) °C ±0.35 °C
B ±(0.30 + 0.005 × |t|) °C ±0.80 °C
C ±(0.60 + 0.01 × |t|) °C ±1.60 °C

Each class applies over a specified temperature range that depends on construction; check the data sheet.

Connection methods and lead-wire error

Cable resistance adds directly to the sensor resistance and is read as temperature.

Connection How it works Typical use
2-wire Lead resistance included in the measurement Short leads, head-mounted transmitters
3-wire Compensates lead resistance if all leads are equal Most industrial installations
4-wire Separate current and measurement leads; eliminates lead resistance Highest accuracy, laboratories, custody transfer

Worked example (illustrative): a 2-wire Pt100 on 50 m of cable with 0.1 Ω per metre per conductor adds 2 × 50 × 0.1 = 10 Ω. At 0.385 Ω/°C, that is an error of about 26 °C. With a 3-wire connection most of this is compensated; with a 4-wire connection it is eliminated. Head-mounted transmitters avoid the problem by converting to 4–20 mA at the sensor. Check conversions with the RTD Calculator.

2-, 3- and 4-Wire RTD Connections: 2-wire (Lead resistance measured, 50 m cable can add about 26 °C); 3-wire (Compensates equal leads, Most industrial installations); 4-wire (Eliminates…
Head-mounted transmitters avoid lead errors by converting at the sensor (illustrative figure).

Self-heating

The measuring current heats the sensor slightly. Keep the current low (typically about 1 mA for a Pt100) and ensure good thermal contact, especially in still air or gas.

Thermistors

Type Behaviour Typical use
NTC (negative temperature coefficient) Resistance falls strongly as temperature rises Temperature measurement in equipment, HVAC, electronics, battery packs
PTC (positive temperature coefficient) Resistance rises sharply above a switching temperature Motor winding protection, overcurrent protection
  • NTC thermistors are very sensitive (several percent resistance change per °C) but strongly non-linear.
  • Linearisation uses the Steinhart–Hart equation (1/T = A + B·ln R + C·(ln R)³) or a B-value approximation over a limited range.
  • Interchangeability between devices is poorer than for standard Pt100s unless matched types are used.
  • PTC thermistors in motor windings are connected to thermistor protection relays and trip the motor at their rated temperature. See Motor Protection.

RTD vs thermistor vs thermocouple

Criterion Pt100 RTD NTC thermistor Thermocouple
Range Wide (cryogenic to several hundred °C) Narrow (typically moderate temperatures) Widest, to very high temperatures
Accuracy and stability High High in a narrow range, poorer interchangeability Lower
Linearity Good Poor (needs linearisation) Moderate
Sensitivity Moderate Very high Low (µV per °C)
Response Moderate Fast (small beads) Fast
Typical industrial use Process temperature, pharma, food, custody transfer Equipment, HVAC, electronics, motor protection (PTC) Furnaces, exhaust, high temperatures

See Thermocouples.

Calibration

  • Compare against a reference thermometer in a dry block or stirred bath at several points covering the working range.
  • For critical measurements, calibrate the sensor and transmitter together (loop calibration) or use sensor-matching: many transmitters accept Callendar–Van Dusen coefficients from a calibrated sensor to reduce error.
  • Record as-found and as-left values. See Calibration and Traceability.

Troubleshooting

Symptom Likely cause First check
Reads high by a steady amount 2-wire lead resistance, wrong wiring configuration Connection type in transmitter; lead resistance
Reads very high or overrange Open circuit Resistance at the sensor terminals
Reads very low Short circuit Insulation and wiring
Unstable reading Moisture in the sensor or head, loose terminal Insulation resistance, terminals
Drift after vibration or shock Damaged element Compare with reference; replace
Reads high in still gas Self-heating Measuring current, thermal contact

Frequently asked questions

What is a Pt100?

A platinum RTD with a resistance of 100 Ω at 0 °C, following the IEC 60751 standard curve (about 0.385 Ω change per °C). It is the most common industrial RTD.

Why use a 3-wire RTD?

A 3-wire connection compensates for the resistance of the connecting cable (assuming equal lead resistances), preventing large temperature errors on long cable runs.

What is the difference between an NTC and a PTC thermistor?

An NTC thermistor’s resistance falls as temperature rises and is used for measurement. A PTC thermistor’s resistance rises sharply above a set temperature and is used mainly for protection, such as motor winding over-temperature.

Key takeaways

  • Pt100 RTDs are accurate, stable and standardised by IEC 60751 classes AA, A, B and C.
  • Use 3- or 4-wire connections or head-mounted transmitters to avoid lead-resistance errors.
  • NTC thermistors are very sensitive but non-linear; PTCs are used for protection.
  • Choose RTD, thermistor or thermocouple by range, accuracy, environment and cost.

Before you apply this in a plant: this article is for education. Always check the current edition of the relevant standards, the manufacturer's documentation for your exact product and version, and your site's procedures. Safety-related work needs qualified personnel. See our editorial policy.

Written by Bhargava Reddy Kapireddy

Bhargava has 16 years of hands-on experience with MES, SCADA, DCS, PLC and industrial data systems across power generation, oil and gas, pharmaceuticals and process manufacturing. He founded MFG Tech Hub to share practical, vendor-neutral automation knowledge.

More about the author → How we write and review articles